The IDC5 can act as either a DC or AC input, accepting 10-32 VDC or 12-32 VAC. All AC and DC input modules have a bridge-rectifier input. Each module provides up to 4000 volts (transient) of optical isolation between the field inputs and the output side of the circuit. Input modules are used for sensing ON/OFF voltage levels. Typical uses and applications include sensing the presence or absence of voltage or sensing contact closures from sources such as: Proximity, limit, selector, photoelectric, toggle, and float switches, push buttons, thermostats, or TTL-compatible devices.
Standard DC Inputs Operating Ambient Temperature - 30 to 70 deg. C Isolation, Input-to-Output (Transient) 4000 V Output Voltage Drop: logic side 0.4 volts @ 50 mA Output Current 50 mA Output Leakage With No Input 0.1 mA @ 30 VDC Transistor 30 volts breakdown DC Input Specifications IDC5 IDC5B Units Input Voltage Range 10 to 32 4 to 16 VDC 12 to 32 4 to 16 VAC Input Current @ Max Line 25 45 mA Turn-on Time 5 0.05 msec Turn-off Time 5 0.1 msec Input Allowed for No Output 1 0.7 mA 3 1 Volts Output Supply 5 5 VDC Voltage-Nominal Output Supply 4.5 to 6 4.5 to 6 VDC Voltage-Range Output Supply Current 12 12 mA @ Nominal Logic Voltage Input Resistance 1.5k 300 Ohms Control Resistance 220 220 Ohms (Rc in schematic diagram) For additional information see: http://www.opto22.com/site/pr_details.aspx?item=IDC5&qs=100310071001,,,17,32& http://relays.tycoelectronics.com/datasheets/IAC_DS.pdf These modules are NEW - with 90 day Warranty Price $6.00 each (4 available) OPTO 22 IDC5 Price $7.00 each (1 available) OPTO 22 IDC5B Price $5.00 each (3 available) Potter & Brumfield IDC-5
|